// 스프링클러설비의 화재안전기준(NFSC 103) 10조 (음향장치 및 기동장치) 2항
Check(NFSC103_10_2){
IF (CS1 THEN KS1) OR (CS2 THEN KS2)
}
CS1{
Space.usage = "RackWarehouse"
isObjectProperty(Space.hasSpecialCombustible) = TRUE
}
KS1{
getObjectHeight(Rack) / 4 = RH
(RH-1) <= getObjectCount(SprinklerHead) < RH
getObjectInterval(SprinklerHead) = 4m
}
CS2{
Space.usage = "RackWarehouse"
isObjectProperty(Space.hasSpecialCombustible) != TRUE
}
KS2{
getObjectHeight(Rack) / 6 = RH
(RH-1) <= getObjectCount(SprinklerHead) < RH
getObjectInterval(SprinklerHead) = 6m
}
|