1
72691
건축물의 에너지절약설계기준 제 5조 5호
5. "고효율에너지기자재인증제품”(이하 "고효율인증제품”이라 한다)이라 함은 산업통상자원부 고시 「고효율에너지기자재 보급촉진에 관한규정」(이하 "고효율인증규정”이라 한다)에서 정한 기준을 만족하여 에너지관리공단에서 인증서를 교부받은 제품을 말한다.
// 옥내소화전설비의 화재안전기준(nfsc 102) 6조 (배관 등) 6항
Check(NFSC102_6_6){
IF (CS1 THEN KS1) OR (CS2 THEN KS2) OR (CS3 THEN KS3) OR (CS4 THEN KS4)
}
Port myPort{
Port.typeForWater = "IndoorFireHydrantDischarge"
}
Pipe myPipe{
isObjectProperty(Pipe.isBranchLines) = TRUE
isConnectedTo(Pipe, myPort) = TRUE
}
Pipe myPipe2{
isObjectProperty(Pipe.isRiser) = TRUE
}
CS1{
getObjectProperty(myPipe.systemType) = "HoseReelHydrantSystem"
}
KS1{
getObjectProperty(myPipe.diameter ) >= 25mm
}
CS2{
getObjectProperty(myPipe.systemType) != "HoseReelHydrantSystem"
}
KS2{
getObjectProperty(myPipe.diameter ) >= 40mm
}
CS3{
getObjectProperty(myPipe2.systemType) = "HoseReelHydrantSystem"
}
KS3{
getObjectProperty(myPipe2.diameter) >= 32mm
}
CS4{
getObjectProperty(myPipe2.systemType) != "HoseReelHydrantSystem"
}
KS4{
getObjectProperty(myPipe2.diameter) >= 50mm
}
Python Code 변환 예정
Modify
2
72696
건축물의 에너지절약설계기준 제 5조 9호 가 목
가. "거실”이라 함은 건축물 안에서 거주(단위 세대 내 욕실·화장실·현관을 포함한다)·집무·작업·집회·오락 기타 이와 유사한 목적을 위하여 사용되는 방을 말하나, 특별히 이 기준에서는 거실이 아닌 냉·난방공간 또한 거실에 포함한다.
// 옥내소화전설비의 화재안전기준(nfsc 102) 6조 (배관 등) 9항
Check(NFSC503A_6_9){
KS
}
KS{
Valve myValve1{
isObjectProperty(Valve.isCheckValve) = TRUE
}
PP = getObjectProperty(Pump.shutoffPressure)
Valve myValve2{
isObjectProperty(Valve.isReliefVavle) = TRUE
isObjectProperty(Valve.reliefPressure) < PP
}
isInstalledInOrder(myValve1, Pipe, Pump) = TRUE
isObjectProperty(Pipe.diameter ) >= 20mm
isInstalled(myValve2, Pipe) = TRUE
}
Python Code 변환 예정
Modify
3
72834
건축물의 에너지절약설계기준 제 11조 1호 마 목
마. 역률개선용콘덴서를 집합 설치하는 경우에는 역률자동조절장치를 설치한다.
// 간이스프링클러설비의 화재안전기준(nfsc 103a) 8조 (배관 및 밸브) 3항 1호
Check(NFSC103A_8_3_1){
IF (CS1 THEN KS1) OR (CS2 THEN KS2)
}
Pipe myPipe{
getObjectProperty(Pipe.usage) = "WaterSupplyType"
isObjectProperty(myPipe.isDirectCoupledType) != TRUE
}
Pipe myPipe2{
getObjectProperty(Pipe.usage) = "WaterSupplyType"
isObjectProperty(myPipe.isDirectCoupledType) = TRUE
}
CS1{
isExist(myPipe) = TRUE
}
KS1{
isObjectProperty(myPipe.isShared) = FALSE
}
CS2{
isExist(myPipe2) = TRUE
}
KS2{
isObjectProperty(myPipe.isShared) = FALSE
getObjectProperty(Pipe.diameter ) >= 32mm
}
Python Code 변환 예정
Modify
4
72844
건축물의 에너지절약설계기준 제 11조 3호 마 목
마. KS A 3011에 의한 작업면 표준조도를 확보하고 효율적인 조명설계에 의한 전력에너지를 절약한다.
// 간이스프링클러설비의 화재안전기준(nfsc 103a) 8조 (배관 및 밸브) 7항
Check(NFSC503A_8_7){
KS
}
KS{
Valve myValve1{
isObjectProperty(Valve.isCheckValve) = TRUE
}
PP = isObjectProperty(Pump.shutoffPressure)
Valve myValve2{
isObjectProperty(Valve.isReliefValve) = TRUE
isObjectProperty(Valve.reliefPressure) < PP
}
isInstalledInOrder(myValve1, Pipe, Pump) = TRUE
isObjectProperty(Pipe.diameter ) >= 20mm
isInstalled(myValve2, Pipe) = TRUE
}
Python Code 변환 예정
Modify
5
72879
건축물의 에너지절약설계기준 제 23조 4 항
④ 기숙사, 오피스텔은 별표1 및 별표3의 공동주택 외의 단열기준을 준수할 수 있으며, 별지 제1호서식의 에너지성능지표 작성 시, 기본배점에서 비주거를 적용한다.
// 간이스프링클러설비의 화재안전기준(NFSC 103A) 별표1 (간이헤드 수별 급수관의 구경) 1항
Check(NFSC103A_*_1){
getResult(NFSC103A_*_1_1) = TRUE
getResult(NFSC103A_*_1_2) = TRUE
getResult(NFSC103A_*_1_3) = TRUE
getResult(NFSC103A_*_1_4) = TRUE
}
Pipe myPipe{
getObjectProperty(Pipe.usage) = "WaterSupplyPipe"
}
Pipe myPipe2{
isObjectProperty(Pipe.isBranchLines) = TRUE
}
PD = getObjectProperty(Pipe.diameter )
SSHN = getObjectCount(SimpleSprinkler.Head.)
Check(NFSC103A_*_1_2){
IF CS THEN KS
}
CS{
Head myHead{
getObjectProperty(SimpleSprinkler.Head.openAndCloseType) = "EnclosedType"
}
isInstalled(myHead) = TRUE
}
KS{
IF PD = 25 THEN SSHN = 2
OR IF PD = 32 THEN SSHN = 3
OR IF PD = 40 THEN SSHN = 5
OR IF PD = 50 THEN SSHN = 10
OR IF PD = 65 THEN SSHN = 30
OR IF PD = 80 THEN SSHN = 60
OR IF PD = 100 THEN SSHN = 100
OR IF PD = 125 THEN SSHN = 160
OR IF PD = 150 THEN SSHN >= 161
}
Check(NFSC103A_*_1_3){
IF CS THEN KS
}
CS{
Head myHead1{
getObjectProperty(SimpleSprinkler.Head.openAndCloseType) = "EnclosedType"
}
isInstalled(myHead1) = TRUE
Head myHead2{
getObjectVerticalLocation(Head, CeilingCovering, ) < 0
}
Head myHead3{
isInstalled(Head, CeilingCovering.Inside) = TRUE
}
isInstalled(myHead2, myPipe2) = TRUE
isInstalled(myHead3, myPipe2) = TRUE
}
KS{
IF PD = 25 THEN SSHN = 2
OR IF PD = 32 THEN SSHN = 4
OR IF PD = 40 THEN SSHN = 7
OR IF PD = 50 THEN SSHN = 15
OR IF PD = 65 THEN SSHN = 30
OR IF PD = 80 THEN SSHN = 60
OR IF PD = 100 THEN SSHN = 100
OR IF PD = 125 THEN SSHN = 160
OR IF PD = 150 THEN SSHN >= 161
}
Python Code 변환 예정
Modify
6
20481
연결송수관설비의 화재안전기준(NFSC 502) 제 5조 4 항
④ 연결송수관설비의 배관은 주배관의 구경이 100㎜ 이상인 옥내소화전설비·스프링클러설비 또는 물분무등소화설비의 배관과 겸용할 수 있다.[종전의 제2항에서 이동 2014.8.18]
//연결송수관설비의 화재안전기준(NFSC 502) 5조 (배관) 4항
Check(NFSC502_5_4){
IF CS THEN KS
}
CS2{
isObjectProperty(Pipe.systemType) = "FireDepartmentConnectionSystem"
}
KS{
Pipe myPipe1{
isObjectProperty(Pipe.isRiser) = TRUE
getObjectProperty(Pipe.diameter ) >= 100mm
isObjectProperty(Pipe.systemType) = "IndoorFireHydrantSystem"
}
Pipe myPipe2{
isObjectProperty(Pipe.isRiser) = TRUE
getObjectProperty(Pipe.diameter ) >= 100mm
isObjectProperty(Pipe.systemType) = "WaterSprayExtingushingSystem"
}
isShared(Pipe,myPipe1) = TRUE
OR isShared(Pipe,myPipe2) = TRUE
OR isShared(Pipe,myPipe1) != TRUE
OR isShared(Pipe,myPipe2) != TRUE
}
Python Code 변환 예정
Modify
7
20102
연소방지설비의 화재안전기준(NFSC 506) 제 4조 4 항 1호
1. 연소방지설비전용헤드를 사용하는 경우에는 다음 표에 따른 구경 이상으로 할 것
//연소방지설비의 화재안전 기준(nfsc 506) 4조 (배관) 4항 1호
Check(NFSC506_4_4_1){
IF CS THEN KS
}
CS{
isInstalled(CombustionProtectionSystem, ?) = TRUE
}
KS{
Pipe myPipe{
hasObject(CombustionProtectionSystem, Pipe) = TRUE
}
SprinklerHead mySprinklerHead{
isInstalled(myPipe, SprinklerHead) = TRUE
}
(getObjectCount(mySprinklerHead) = 1
getObjectProperty(myPipe.Diameter) >= 32mm)
OR(getObjectCount(mySprinklerHead) = 2
getObjectProperty(myPipe.Diameter) >= 40mm)
OR(getObjectCount(mySprinklerHead) = 3
getObjectProperty(myPipe.Diameter) >= 50mm)
OR(getObjectCount(mySprinklerHead) = 4
getObjectProperty(myPipe.Diameter) >= 65mm)
OR(getObjectCount(mySprinklerHead) = 5
getObjectProperty(myPipe.Diameter) >= 65mm)
OR(getObjectCount(mySprinklerHead) >= 6
getObjectProperty(myPipe.Diameter) >= 80mm)
}
Python Code 변환 예정
Modify
8
20104
연소방지설비의 화재안전기준(NFSC 506) 제 4조 5 항
⑤연소방지설비에 있어서의 수평주행배관의 구경은 100㎜ 이상의 것으로 하되, 연소방지설비전용헤드 및 스프링클러헤드("방수헤드"라 한다. 이하 같다)를 향하여 상향으로 1,000분의 1 이상의 기울기로 설치하여야 한다.<개정 2012.8.20>
// 연소방지설비의 화재안전기준(nfsc 506) 4조 (배관) 5항
Check(NFSC506_4_5){
KS
}
KS{
Pipe myPipe{
isObjectProperty(Pipe.isFeedMains) = TRUE
}
isInstalled(myPipe, CombustionProtectionSystem) = TRUE
getObjectProperty(myPipe.diameter ) >= 100mm
}
Python Code 변환 예정
Modify