// 비상콘센트설비의 화재안전기준(nfsc 504) 4조 (전원 및 콘센트 등) 1항 2호
Check(NFSC504_4_1_2){
IF CS THEN KS
}
Floor myFloor{
getFloorNumber < 0
hasSpace(Floor, SpecificFireFightingBuilding) = TRUE
}
Floor myFloor2{
getFloorNumber >= 0
hasSpace(Floor, SpecificFireFightingBuilding) = TRUE
}
CS{
(getBuildingStoriesCount() >= 7
getGrossFloorArea(myFloor2) >= 2000m2)
OR getTotalFloorArea(myFloor) >= 3000m2
}
KS{
isInstalled(EmergencyPower, EmergencyPowerOutletSystem) = TRUE
getObjectProperty(EmergencyPowerReceivingSystem.type) = "InhousePowerGenerationSystem"
OR getObjectProperty(EmergencyPowerReceivingSystem.type) = "EmergencyPowerReceivingSystem"
}
|
Python Code 변환 예정
|