// 연결살수설비의 화재안전기준(nfsc 503) 5조 (배관 등) 2항 1호
Check(NFSC503_5_2_1){
IF CS THEN KS
}
CS{
getObjectProperty(Head.systemType) = "HookingUpSprinklerSystem"
isObjectProperty(Head.isShared) = FALSE
}
KS{
Head myHead{
isInstalled(Head., Pipe.One) = TRUE
}
NH = getObjectCount(myHead)
IF NH = 1 THEN getObjectDiameter(Pipe) >= 32mm
ELSE IF NH = 2 THEN getObjectDiameter(Pipe) >= 40mm
ELSE IF NH = 3 THEN getObjectDiameter(Pipe) >= 50mm
ELSE IF NH = 4 OR NH = 5 THEN getObjectDiameter(Pipe) >= 65mm
ELSE IF NH >= 6 AND HN <= 10 THEN getObjectDiameter(Pipe) >= 80mm
}
// 연결살수설비의 화재안전기준(nfsc 503) 5조 (배관 등) 2항 2호
Check(NFSC503_5_2_2){
IF CS THEN KS
}
CS{
isObjectProperty(SprinklerSystem.Head.systemType) = "HookingUpSprinklerSystem"
}
KS{
getResult(NFSC103_*_1) = TRUE
}
|
Python Code 변환 예정Python Code 변환 예정
|